2.4 Instruction Details
1
2
3-107
Chapter 2 Instructions
Note 1: The following table shows the status of each instruction between STG and
JMP/ENDS when STG operand relay turns OFF.
Note 2: STG/JMP/ENDS operand relay Nos. cannot be duplicated in a program.
Note 3: The STG instruction must be used in combination with the JMP or ENDS
instruction.
Note 4: The following instructions are not properly executed between STG and JMP/
ENDS instructions:
DIFU, DIFD, KEEP, UDC, SFT, FOR, NEXT, and
Differentiation type instruction (@xxx)
Operands
* Note that of I/O Nos. 7000 to 9915, those that are not assigned to expansion or
remote I/O unit ports can be used for internal utility relays.
Key operation
FUN
FUN
ANL
2
FUN
LDB
4
LDB
4
LDB
4
SET
1
SET
1
Operand
(nnnn)
Operand
(nnnn)
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
ENT
R-SRCH
Instruction Function
Relay for OUT instruction Turned OFF.
Relay for OUB instruction Turned ON.
TMR, TMH, TMS, Reset.
C (counter) instructions
SET, RES instructions Current status is retained.
Other instructions Not executed.
STG / JMP / ENDS
Visual KV KV-300 KV-10/16 KV-24/40/80
1000 to 1915 1000 to 1915 1000 to 1915 1000 to 1915
3000 to 9915 3000 to 6915
*7000 to 9915
KVNKA Chap 02_4bP.p65 08.3.11, 0:00 PM107