2-2 Wiring
2-7
2
Connection and Configuration
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
2
Trim the shield.
Upbraid the shield braid carefully. Find the bare drain wire (twisted or flying)
inside the shield braid. Twist together the unbranded shield braid and the drain
wire securely, and then put on the insulating tube.
3
Strip the sheathed conductors.
Strip approximately 10 mm of sheath from each signal wire, by removing the
aluminum polyester laminated tape. Take care not to damage the signal wires.
Twist together the exposed conductors securely.
If you are using solderless terminals, perform cable wiring/
trimming appropriately to suit the specifications of the partic-
ular terminals.
Recommended solderless terminals: Phoenix Contact's A/AI
Series
Do not perform soldering (pre-soldering) on the trimmed end
of the cable.
Aluminum polyester laminated tape
Insulating tube
Shield braid twisted together
Twist together the conductors
Approx. 10 mm
Point