4-2 Basic Settings and Advanced Settings
4-30
4
Setting Various Functions
IB-E
Zero shift input
When the zero shift input is set to ON, the internal measurement value (R.V.) is shifted
(offset) to an arbitrary shift target value.
"3-7 Zero Shift Function (Shifting the Internal Measurement Value (R.V.))" (page 3-18)
Timing chart
Minimum input time
ON time: 2 ms
OFF time: 2 ms
Reset input
When the reset input is turned ON while using the hold function, the judgment value (P.V.)
in the held state is canceled and the value becomes [-----].
" 5. Hold Function" (page 4-14)
Timing chart
Minimum input time
ON time: 0.5 ms
OFF time: 0.5 ms
Internal measurement
value (R.V.)
Max. 6 ms
Min. 2 msMin. 2 ms
R.V. before shift R.V. after shift
ON
OFF
Zero shift input
Judgment value (P.V.)
judgment output
Max. 0.5 ms
Min. 0.5 ms
Min. 0.5 ms
Before resetting [-----]
ON
OFF
Reset input