Keyence IV Series Manuel d'utilisateur Page 67

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 110
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 66
5-9
- IV Series Users Manual (Field Network) -
Data I/O communication setting method
11
Click the [Properties] tab. Select
[PROFINET interface [x1]] - [Ethernet
addresses] under [General], and then
select the IP address setting method for
the IV series.
To set a new IP address for the IV series
using the DCP protocol
To use the IP address that is already
registered for the IV series
If the IP address will be set by the DCP
protocol, the IP address of the sensor will be
initialized.
The IP address set by the DCP protocol will
be stored in the volatile memory.
When you restart the sensor, the sensor
will start up with its IP address in “----”
(unregistered) status.
12
Click the [Properties] tab. Select
[PROFINET interface [x1]] - [Advanced
options] - [Real time settings] in
[General], and then set the SendCycle
(communication cycle) for the data I/O
communication in [Update time].
13
Click the CPU in the [Devices] tab. Select
[Compile] - [All] and save the settings.
5
Data I/O communication
Vue de la page 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 109 110

Commentaires sur ces manuels

Pas de commentaire