5-20
- IV Series Users Manual (Field Network) -
Data allocations in the data I/O communication
Control Modules parameter details
Command Control Address 0 to 1: Control request
The Bits at Address 0 to 1 of the Command Control have the following functions:
Address Bit Item Content Data content
0
0 Trigger request Requests the external trigger.
0 : OFF
1 : ON
1
Master image registration
request
Requests a master image
registration.
0 : OFF
1 : ON
2
Program switching
request
Requests a program switching.
0 : OFF
1 : ON
3 Warning clear request Requests a warning clear.
0 : OFF
1 : ON
4 Statistics reset request Requests a statistics reset.
0 : OFF
1 : ON
5 Buffer clear request Requests a buffer clear.
0 : OFF
1 : ON
6 to 7 Reserved by system --- ---
1 0 to 7 Reserved by system --- ---
The following will occur when a buffer clear is requested:
If handshake control is [Enabled]
The current status result will be cleared.
The status result in the buffer will be cleared.
The result available bit will become OFF (0).
The number of remaining buffers will become “10”.
If handshake control is [Disabled]
The current status result will be cleared.
The result available bit will become OFF (0).
If you are switching programs using the PROFINET communication, set the [Switching method]
option to [Monitor/PC]. For details of the setting, Refer to the “IV Series User’s Manual (Monitor / PC
Software)”.
Buffer overrun and warning statuses will not be cleared even if you execute a buffer clear request.