5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
5-10
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -
5
Appendix
2
Add the MSG instruction to the RsLogix5000 ladder.
3
Open the "Configuration" tab in the Message instruction setting dialog,
and change the MSG instruction setting.
Message Type
Select "CIP Generic".
ServiceType, Class, Instance, Attribute
Designate a value which matches the message to be sent.
Example 1: Writing data to DL Object "Bank 0 HIGH setting" when writing
data to attributes
Item Setting Value
ServiceType SetAttributeSingle
ServiceCode - (Cannot be designated)
Class 67H
Instance 01H
Attribute 0341H
SourceElement Name of tag storing send data
SourceLength 4 byte (attribute size is 4)
Destination - (Cannot be designated)